Columns in RCC are vertical members that transfer loads safely to the foundation. These GATE Civil Engineering notes cover types of RCC columns, components, design principles, detailing as per IS codes, and key formulas, helping aspirants strengthen concepts for exams and practice.

authorImageAnanya Gupta21 Jan, 2026
Columns in RCC: GATE Civil Engineering Notes

Columns in RCC are vertical structural members that play a vital role in the safety and stability of a building. They are designed to carry loads from slabs and beams and transfer them safely to the foundation. In reinforced concrete structures, columns work by combining the compressive strength of concrete with the tensile strength of steel reinforcement. 

Proper design and detailing of RCC columns ensure adequate load-carrying capacity, prevent buckling, and improve the overall durability of the structure. Because of their critical function, understanding RCC columns is essential for civil engineering studies as well as practical construction work.

What is a Column?

A column is a vertical structural member designed to support axial loads, either compressive or combined axial and bending loads. In RCC structures, columns are generally made of concrete and steel reinforcement, where the concrete resists compression, and the steel resists tension.

  • Primary Function: Transfer loads safely from the superstructure to the foundation.

  • Other Functions: Provide stability to the structure, prevent buckling, and sometimes resist lateral loads.

Classification of RCC Columns

RCC columns can be classified based on geometry, slenderness, and reinforcement.

1. Based on Cross-Section

  • Rectangular or Square Columns: Common in residential buildings, easy to construct.

  • Circular Columns: Typically used in bridges, water tanks, or architectural aesthetics.

  • L-Shaped & T-Shaped Columns: Used at corners or junctions to resist bending in multiple directions.

2. Based on Slenderness

  • Short Columns: Slenderness ratio λ=leffb<12\lambda = \frac{l_{eff}}{b} < 12λ=bleff​​<12. Failure occurs mainly by compression.

  • Long/Slender Columns: Slenderness ratio λ>12\lambda > 12λ>12. Failure occurs due to buckling.

3. Based on Reinforcement

  • Tie Column: Reinforced with longitudinal bars tied with lateral ties.

  • Spiral Column: Reinforced with spiral reinforcement, providing better ductility.

Check: GATE Civil Engineering Notes

Components of RCC Columns

An RCC column is made up of several important components that work together to safely carry loads and maintain structural stability. Each component has a specific role in strength, durability, and safety.

1. Concrete Core

The concrete core is the main body of the column. Its primary function is to resist compressive loads coming from slabs and beams. Concrete also helps in protecting the steel reinforcement from corrosion, fire, and environmental effects. The strength of the column largely depends on the grade of concrete used, such as M20, M25, or higher.

2. Longitudinal Reinforcement

Longitudinal reinforcement consists of steel bars placed vertically along the length of the column. These bars help the column resist axial loads and bending moments caused by eccentric loading or lateral forces like wind and earthquakes.
Key points:

  • Minimum 4 bars are required in rectangular columns and 6 bars in circular columns.

  • Bars are placed uniformly to ensure balanced load distribution.

  • Common steel grades used are Fe415 and Fe500.

3. Lateral Ties / Stirrups

Lateral ties (also called stirrups) are horizontal steel bars that wrap around the longitudinal bars. Their main function is to prevent buckling of the vertical reinforcement under compression. They also help in confining the concrete, which increases the ductility and strength of the column, especially during earthquakes.
Important details:

  • Tie spacing is closer near column ends (usually 75 mm) and wider at mid-height (about 150 mm), as per IS 456.

  • The diameter of ties generally ranges from 8 mm to 12 mm.

4. Clear Cover

Clear cover is the distance between the outer surface of the concrete and the nearest steel reinforcement. It is provided to protect steel bars from corrosion, fire, and weather effects. Adequate cover also improves the durability of the column.

  • As per IS 456, the minimum clear cover for columns is 25 mm.

5. Column Ends (Top and Bottom Zones)

The top and bottom regions of a column are critical because they experience higher stress concentrations due to load transfer. Hence, closer spacing of ties is provided in these regions to improve confinement and prevent premature failure.

6. Reinforcement Arrangement

Proper arrangement of reinforcement ensures uniform stress distribution and structural safety. Bars should be placed symmetrically, and ties must be properly anchored with hooks to ensure effective confinement.

Design Considerations for RCC Columns

When designing RCC columns, the following factors must be considered:

  • Axial Load (P): The vertical load carried by the column.

  • Bending Moment (M): Induced by eccentricity or lateral loads.

  • Slenderness Ratio (λ\lambdaλ): Determines whether the column is short or slender.

  • Material Properties: Concrete grade (M20, M25, etc.) and steel grade (Fe415, Fe500).

  • Effective Length (l_eff): Depends on end conditions (pinned, fixed, or free).

Design Considerations for RCC Columns

End Condition

Effective Length Factor (k)

Both ends pinned

1.0

One end fixed, one end free

2.0

Both ends fixed

0.5

One end fixed, one end pinned

0.7

Design of Short Columns

For short columns, failure occurs due to crushing of concrete.

  • Axially Loaded Columns:

    • Design is based on the ultimate load method (limit state method).

    • Reinforcement is provided according to the axial load and bending moment.

  • Axially Loaded with Bending:

    • Consider eccentricity of load e=MPe = \frac{M}{P}e=PM​.

    • Use interaction curves to check the adequacy of the section.

Detailing of RCC Columns

Proper detailing of RCC columns is essential to ensure the strength, safety, durability, and good performance of the structure, especially under heavy loads and seismic forces. Even a well-designed column can fail if detailing is not done correctly.

1. Longitudinal Reinforcement Detailing

Longitudinal bars are placed vertically to carry axial load and bending.

  • Minimum number of bars

    • Rectangular/Square column: 4 bars

    • Circular column: 6 bars

  • Bar diameter

    • Commonly used diameters: 12 mm, 16 mm, 20 mm, or 25 mm

    • Spacing of bars

    • Bars should be placed uniformly along the perimeter

    • The clear distance between bars should not be less than the bar diameter or 20 mm, whichever is greater

  • Lap splices

    • Provided where bar length is insufficient

    • Laps should be placed away from regions of maximum stress

    • Not more than 50% of bars should be lapped at one section

2. Lateral Ties / Stirrups Detailing

Lateral ties hold longitudinal bars in position and prevent buckling.

  • Purpose of ties

    • Prevent buckling of vertical bars

    • Confine concrete and improve ductility

    • Increase column strength during earthquakes

  • Diameter of ties

    • Minimum 8 mm (can be 10 mm or 12 mm for larger columns)

  • Spacing of ties (as per IS 456)

    • Not more than the least of:

      • The least lateral dimension of the column

      • 16 times the smallest longitudinal bar diameter

      • 300 mm

    • Near top and bottom ends: closer spacing (about 75 mm)

    • Mid-height of column: up to 150 mm

  • Tie shape and hooks

    • Ties should be properly closed with 135° hooks

    • Hooks must have adequate extension for proper anchorage

3. Clear Cover

Clear cover protects steel from corrosion, fire, and environmental effects.

  • Minimum clear cover for columns: 25 mm

  • In aggressive environments, higher cover may be required

4. Detailing at Column Ends

The top and bottom zones of a column are critical due to load transfer from beams and footing.

  • Provide closer tie spacing near both ends

  • Ensures better confinement and prevents crushing or buckling

5. Seismic Detailing (Special Cases)

In earthquake-prone areas, additional detailing is required as per IS 13920.

  • Closer tie spacing in plastic hinge zones

  • Special confining reinforcement

  • Improved ductility and energy dissipation capacity

Elevate your GATE readiness with Physics Wallah’s GATE Online Courses. PW GATE Online Coaching offers comprehensive live sessions tailored to the syllabus, invaluable study materials, practice tests, and much more.

 

Columns in RCC FAQs

What is an RCC column?

A vertical structural member that transfers loads from beams and slabs to the foundation.

What are lateral ties for?

Prevent buckling of steel bars and confine concrete.

What is effective length?

The length between lateral supports, used for buckling calculations.

Slenderness ratio significance?

Determines whether the column will fail by compression or buckling.
Free Learning Resources
Know about Physics Wallah
Physics Wallah is an Indian edtech platform that provides accessible & comprehensive learning experiences to students from Class 6th to postgraduate level. We also provide extensive NCERT solutions, sample paper, NEET, JEE Mains, BITSAT previous year papers & more such resources to students. Physics Wallah also caters to over 3.5 million registered students and over 78 lakh+ Youtube subscribers with 4.8 rating on its app.
We Stand Out because
We provide students with intensive courses with India’s qualified & experienced faculties & mentors. PW strives to make the learning experience comprehensive and accessible for students of all sections of society. We believe in empowering every single student who couldn't dream of a good career in engineering and medical field earlier.
Our Key Focus Areas
Physics Wallah's main focus is to make the learning experience as economical as possible for all students. With our affordable courses like Lakshya, Udaan and Arjuna and many others, we have been able to provide a platform for lakhs of aspirants. From providing Chemistry, Maths, Physics formula to giving e-books of eminent authors like RD Sharma, RS Aggarwal and Lakhmir Singh, PW focuses on every single student's need for preparation.
What Makes Us Different
Physics Wallah strives to develop a comprehensive pedagogical structure for students, where they get a state-of-the-art learning experience with study material and resources. Apart from catering students preparing for JEE Mains and NEET, PW also provides study material for each state board like Uttar Pradesh, Bihar, and others

Copyright © 2026 Physicswallah Limited All rights reserved.